Custom-built industrial electrical panels designed on EPLAN, manufactured in our facility, and tested to IEC 61439 standards. From a simple MCC starter panel to a fully integrated PLC SCADA control system — we make what your plant needs. Plus DG set sales, service, and electrical licensing work.
We design on EPLAN and manufacture CPRI type-tested PCC, MCC, and PLC automation panels (up to 6300A busbar rating) using 100% Tier-1 switchgear for factories, solar plants, and substations.
CPRI type-tested PCC, MCC, PLC panels up to 6300A busbar rating with 100% Tier-1 switchgear components.
Main Power Control Centre panels rated up to 6300A with 65kA / 1 sec short-circuit withstand capacity, 99.9% ETP grade copper busbars, and Form 4b fully compartmentalized steel enclosures.
Fully compartmentalized MCC panels housing star-delta starters, soft starters, and VFD drives with withdrawable drawer units for rapid maintenance and minimal process downtime.
11kV/33kV vacuum circuit breaker panels and SF6 Ring Main Units (RMU) for factory receiving substations, equipped with microprocessor-based protection relays (Siemens/Schneider).
Turnkey PLC programming and SCADA integration (Siemens S7-1500, Allen-Bradley CompactLogix), HMI touchscreens, Profinet fieldbus wiring, and plant process automation.
Comprehensive schematic drafting on EPLAN P8 and AutoCAD Electrical — multi-line wiring diagrams, terminal strip mapping, cross-referencing, and complete Bill of Materials (BOM).
Diesel generator sales (15 kVA to 2000 kVA), auto-mains failure (AMF) panels, multi-DG synchronization panels, and statutory CEIG electrical inspector clearance.
You share your single-line diagram or load list. We review motor ratings, protection requirements, fault levels, and control philosophy.
Detailed EPLAN schematics created — power circuit, control circuit, wiring diagram, and terminal strip layout sent for your approval.
CNC sheet metal fabrication, busbar bending, component mounting, wire ferrule marking, and Factory Acceptance Testing (FAT).
Site installation, cable termination, interlocking check, PLC I/O checkout, and final Site Acceptance Testing (SAT).
Switchgear ratings, CPRI short-circuit withstand capabilities, and PLC/SCADA automation standards.
| Technical Parameter | Engineering Specification | Applicable Standard |
|---|---|---|
| Busbar Current Rating | Up to 6300A High-Purity ETP Copper / Electrolytic Aluminium | CPRI Tested (65kA for 1 sec) |
| Design & Enclosure Standard | 2.0mm CRCA Sheet Metal, Powder Coated RAL 7035 (IP42 to IP65) | IEC 61439-1/2 / IS 8623 |
| Form of Separation | Form 1 to Form 4b Fully Compartmentalized Withdrawable Drawers | Form 4b Safety Isolation Code |
| Switchgear Components | Tier-1 OEM Switchgear (Schneider Electric, Siemens, ABB, L&T) | 100% Original Factory Equipment |
| PLC & SCADA Hardware | Siemens SIMATIC S7-1500/1200, Allen-Bradley CompactLogix | Profinet / Modbus TCP Protocols |
| Schematics & Blueprints | EPLAN Electric P8 Multi-Line Schematics & Wire Tagging BOM | IEC 81346 Standard |
| DG Set & AMF Panels | 15 kVA to 2000 kVA DG Sync Panels with AMF Controllers | CEIG / CPCB-IV+ Approved |
EPLAN schematic design, Tier-1 components, and CPRI type-tested reliability.
Every panel starts with a formal EPLAN schematic — approved by you before manufacturing begins. Wire numbers, terminal strips, and tags are fully mapped.
Schneider, Siemens, ABB, L&T. We never use cheap unbranded components. Every MCCB, contactor, relay, and meter comes with OEM test certificates.
Our PCC and MCC designs are type-tested at CPRI laboratories for temperature rise, short-circuit withstand (65kA), and insulation coordination.
We don't drop panels at your gate and walk away. We install them, terminate cabling, commission automation, and secure CEIG electrical licensing.
Share your single-line diagram, motor list, or equipment schedule. Our panel engineering team will send you a detailed factory-direct quotation within 24 working hours.